Indoor Environmental Quality General Assessment of Deep Run Elementary School: December 8th, 2020 (GXDRES202000002D)

Assessor
Christopher Madden
Date

Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)

Ductwork (Supply and Return)
Check OK Comments
Condition
No odors, noise or vibration
No
Gymnasium - Ductwork rattling (WO #175503)
Clean, no obstructions
No
B135 - Return grille dirty. C210 and A155 - HVAC returns are blocked.
Free from signs of moisture/mold, insects or rodents?
Yes
No noticeable air leaks
Yes
Duct Lining
No dirt, dampness, or mold
Yes
No Deterioration
No
A163 - Fiberglass duct insulation has come unwrapped from duct (~ 10 Linear Feet, WO #175533)
Plenum
Check OK Comments
Ceiling Tiles
Tight seal on all tiles
No
C214 - 2 Tiles not seated into grid. Boys Bathroom (Next to B174) and C111 - Missing ceiling tile(s).
No stained/damaged tiles indicating high RH or moisture problem
Yes
Supply Diffusers, Return Grilles, Exhaust Grilles
Check OK Comments
Condition
No odors or unusual sounds
Yes
Clean, no excess dirt or moisture
Yes
No obstruction to air flow
Yes
No purposely placed obstruction indicating occupant distress
Yes
Location
No short circuiting between supply and return
Yes
Doors
Doors not tight or difficult to close indicating large pressure differential
Yes

Building

Envelope
Check OK Comments
Foundation
No moisture penetration or signs of mold?
Yes
Doors and Windows
Caulking and weather stripping in good condition
Yes
Classrooms (Assess 2 to 3 per HVAC System Zone)
Check OK Comments
Condition
Room is free of dust and clutter
Yes
No stained or damage ceiling tiles
Yes
No visible mold present (walls, cabinets, under sinks, behind posters)
Yes
Relative Humidity
Not above 70%
Yes
Mechanical/Boiler Rooms (Assess Each)
Check OK Comments
Condition
Clean
Yes
No unusual noise or odor
Yes
No mold growth on insulation
Yes
Traps contain water
Yes
Chemical Storage
Containers capped
No
Custodial Storage Area (off Cafeteria) - Unlabeled, uncapped spray bottle.
No evidence of an active spill
Yes
Fan Coil Units/VAV Boxes
Check OK Comments
Condition
No odors, or unusual noise or vibration
Yes