Assessor
Jeffrey Klenk
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
Yes
|
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes Work Order Closed by Building Maintenance
|
Room C08 smelled of an air freshener / odorizer. An air freshener was observed. School administration is to have the air freshener removed and inform staff such products are prohibited since they can mask an odor of concern and/or be a nuisance or irritant to sensitive individuals.
|
Clean, no excess dirt or moisture
|
Yes
|
|
No obstruction to air flow
|
Yes Work Order Closed by Building Maintenance
|
Clutter was on and/or around the ventilation unit along the wall of room B04. School administration is to inform staff not to obstruct ventilation equipment.
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
Yes
|
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
Yes Work Order Closed by Building Maintenance
|
Mineral salts (from moisture intrusion of failed window flashing details) observed forming around windows of room A07 (front left window), cafeteria room C10 (left window, upper right side), and hallway across from room D08 (left window, upper right side). Until Building Maintenance corrects source and refinish interior damage, school administration is to make staff aware not to attach items with an impermeable barrier (i.e. laminate, plastic, glossy coating) on exterior walls near windows since mold can form behind the items against the block wall. The items may serve as a vapor barrier and trap water vapor. Work order 234544 issued to Building Maintenance to review.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
Yes Work Order Closed by Building Maintenance
|
Food accessible to pests were observed in rooms B04, C10, and D05. If food items are necessary to be in the classroom, they are to be in sealed containers. School administration is to inform staff.
Some of the media shelving had moderate dust accumulation. School custodial staff is to clean at this time and then follow scheduled cleaning frequency.
Aerosol disinfectant sprays and/or non-HCPSS chemicals were observed in rooms B62 and D29. These were also accessible to students (not stored out of reach). An empty spray bottle was observed at sink in room D05. School administration is to inform staff these products are not allowed within the building. Only use HCPSS issued cleaning / disinfecting products. Spray bottles are to be properly labeled with manufacturer's secondary container labels and must be a HCPSS custodial product.
|
No stained or damage ceiling tiles
|
Yes Work Order Closed by Building Maintenance
|
Water stained ceiling tiles in hallway outside of room C37 and A67. If not already being addressed, school custodial staff is to submit a work order to Building Maintenance to assess and correct source of the leak.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes Work Order Closed by Building Maintenance
|
Student desks were up against the ventilation equipment along the wall in room D05. However, desks should not be placed near the ventilation unit to avoid potential drafts from the supply air discharge to nearby students. School administration is to inform staff to ensure students are not bothered by the airflow and move desks away from the ventilation as necessary.
|
Work Order Number(s)
234544
Issues found durring this assessment have been assigned to the above
work order(s).