Indoor Environmental Quality General Assessment of Ducketts Lane Elementary School: April 14th, 2021 (GXDLES2021000042)

Assessor
Jeffrey Klenk
Date

Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)

Ductwork (Supply and Return)
Check OK Comments
Condition
No odors, noise or vibration
Yes
Clean, no obstructions
Yes
Free from signs of moisture/mold, insects or rodents?
Yes
No noticeable air leaks
Yes
Plenum
Check OK Comments
Ceiling Tiles
Tight seal on all tiles
Yes
No stained/damaged tiles indicating high RH or moisture problem
Yes
Supply Diffusers, Return Grilles, Exhaust Grilles
Check OK Comments
Condition
No odors or unusual sounds
Yes
Clean, no excess dirt or moisture
Yes
No obstruction to air flow
No
Room A147, the return air grille on the wall is partially obstructed by items. School administration is inform staff to remove items and keep vents free of obstruction. B131 (and possibly other areas served in the same HVAC zone) air handling system was off as scheduled, but local exhaust in the classroom and its restroom were operating. Work order 187645.
No purposely placed obstruction indicating occupant distress
Yes
Location
No short circuiting between supply and return
Yes
Doors
Doors not tight or difficult to close indicating large pressure differential
Yes

Building

Envelope
Check OK Comments
Foundation
No moisture penetration or signs of mold?
Yes
Doors and Windows
Caulking and weather stripping in good condition
Yes
Classrooms (Assess 2 to 3 per HVAC System Zone)
Check OK Comments
Condition
Room is free of dust and clutter
Yes
No stained or damage ceiling tiles
Yes
No visible mold present (walls, cabinets, under sinks, behind posters)
Yes
Relative Humidity
Not above 70%
Yes
Mechanical/Boiler Rooms (Assess Each)
Check OK Comments
Condition
Clean
Yes
No unusual noise or odor
Yes
No mold growth on insulation
Yes
Traps contain water
Yes
Chemical Storage
Containers capped
No
Some student restrooms house custodial closets (contains chemical products) that are not readily visible from the hallway. Custodial closet A207 was unlocked. School custodial staff are to ensure custodial closets are secured when not in use.
No evidence of an active spill
Yes
Fan Coil Units/VAV Boxes
Check OK Comments
Condition
No odors, or unusual noise or vibration
No
The two wall mounted air conditioning units in server room B203 (outside of media) have grime forming on components. Work order 187646.