Indoor Environmental Quality General Assessment of Bushy Park Elementary School: July 7th, 2022 (GXBPES20220000A0)

Assessor
Christopher Madden
Date

Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)

Ductwork (Supply and Return)
Check OK Comments
Condition
No odors, noise or vibration
Yes
Clean, no obstructions
Yes
Work Order Closed by Building Maintenance
216 - Supply diffusers vents dusty (Custodial). Gym - Return vent dusty (Custodial).
Free from signs of moisture/mold, insects or rodents?
Yes
No noticeable air leaks
Yes
Plenum
Check OK Comments
Ceiling Tiles
Tight seal on all tiles
Yes
Work Order Closed by Building Maintenance
Vestibule Near Stairwell 3 - Ceiling tile out of place (reset during assessment).
No stained/damaged tiles indicating high RH or moisture problem
Yes
Supply Diffusers, Return Grilles, Exhaust Grilles
Check OK Comments
Condition
No odors or unusual sounds
Yes
Clean, no excess dirt or moisture
Yes
No obstruction to air flow
Yes
No purposely placed obstruction indicating occupant distress
Yes
Location
No short circuiting between supply and return
Yes
Doors
Doors not tight or difficult to close indicating large pressure differential
Yes

Building

Envelope
Check OK Comments
Foundation
No moisture penetration or signs of mold?
Yes
Doors and Windows
Caulking and weather stripping in good condition
Yes
Work Order Closed by Building Maintenance
Gym - Daylight at exterior doors (WO #244290).
Classrooms (Assess 2 to 3 per HVAC System Zone)
Check OK Comments
Condition
Room is free of dust and clutter
Yes
Work Order Closed by Building Maintenance
Room 101 - Excessive stuffed animals (dust collectors). If Administration decides they serve an educational purpose the staff member who brought them in is responsible for the routine cleaning of the items. Room 137 - Dead bugs in light fixture (Custodial).
No stained or damage ceiling tiles
Yes
Work Order Closed by Building Maintenance
116/119 Storage, Custodial Office, 137, Outside 211, and Outside 216 - Stained Ceiling Tile. Please place a work order for Building Maintenance to address the cause of the leak if a work order is not in progress already.
No visible mold present (walls, cabinets, under sinks, behind posters)
Yes
Work Order Closed by Building Maintenance
Kitchen - Condensation on metal freezers. This can cause mold growth during the summer that requires occasional wipe down with a cloth and soap/water or the cleaner normally used on stainless steel.
Relative Humidity
Not above 70%
Yes
Mechanical/Boiler Rooms (Assess Each)
Check OK Comments
Condition
Clean
Yes
No unusual noise or odor
Yes
No mold growth on insulation
Yes
Traps contain water
Yes
Chemical Storage
Containers capped
Yes
No evidence of an active spill
Yes
Fan Coil Units/VAV Boxes
Check OK Comments
Condition
No odors, or unusual noise or vibration
Yes
Work Order Number(s)
244290
Issues found durring this assessment have been assigned to the above work order(s).