School
Assessor
Christopher Madden
Date
Air Distribution and Terminal System (Assess 2-3 Locations per HVAC Zone)
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, noise or vibration
|
Yes
|
|
Clean, no obstructions
|
Yes
|
|
Free from signs of moisture/mold, insects or rodents?
|
Yes
|
|
No noticeable air leaks
|
Yes
|
Check | OK | Comments |
---|---|---|
Ceiling Tiles | ||
Tight seal on all tiles
|
No
|
Outside of Room 44 - Missing Ceiling Tile.
|
No stained/damaged tiles indicating high RH or moisture problem
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors or unusual sounds
|
Yes
|
|
Clean, no excess dirt or moisture
|
Yes
|
|
No obstruction to air flow
|
Yes
|
|
No purposely placed obstruction indicating occupant distress
|
Yes
|
|
Location | ||
No short circuiting between supply and return
|
Yes
|
|
Doors | ||
Doors not tight or difficult to close indicating large pressure differential
|
Yes
|
Building
Check | OK | Comments |
---|---|---|
Foundation | ||
No moisture penetration or signs of mold?
|
No
|
Interior Stairwells - Peeling paint indicative of moisture intrusion, possibly windows (WO #124153).
|
Doors and Windows | ||
Caulking and weather stripping in good condition
|
No
|
Exterior of Building (Throughout) - Various areas of damaged vertical caulk (WO #124153).
Mortar joints missing steel wool/weep vent to deter pests (IPM alerted via email).
|
Check | OK | Comments |
---|---|---|
Condition | ||
Room is free of dust and clutter
|
No
|
Classroom 2 - Fan Coil Unit blocked with chair, corrected while onsite.
|
No stained or damage ceiling tiles
|
No
|
Computer Lab - Multiple Stained Ceiling Tiles.
|
No visible mold present (walls, cabinets, under sinks, behind posters)
|
Yes
|
|
Relative Humidity | ||
Not above 70%
|
No
|
Portable 75 - The humidity was not above 70% at the time of measurement. However, the thermostat cover was missing and the thermostat was incorrectly set with the Fan "On" (instead of Auto). This setting can cause mold growth in the summer. The thermostat setting was corrected while onsite. A thermostat cover needs to be re-installed (WO #162587). No mold growth was identified.
|
Check | OK | Comments |
---|---|---|
Condition | ||
Clean
|
Yes
|
|
No unusual noise or odor
|
Yes
|
|
No mold growth on insulation
|
Yes
|
|
Traps contain water
|
Yes
|
|
Chemical Storage | ||
Containers capped
|
Yes
|
|
No evidence of an active spill
|
Yes
|
Check | OK | Comments |
---|---|---|
Condition | ||
No odors, or unusual noise or vibration
|
Yes
|