Concern: Atholton Elementary School: August 7th, 2026 (CXXAES20260003CC)

Location
Room 111
Date of IEQ Report Form
Date of Report
Concern
Mold Athloton Elementary school
IEQ Investigation Process

Identify deficiencies that may impact IEQ and/or sources of odor concerns. Typically includes the following depending on the nature of concern, but not limited to:

  • interview/questionnaire of concern individual(s)
  • inspection above drop ceiling (condition of roof deck, pipe insulation, return air plenum)
  • inspection of ventilation system (operation of variable air volume box and outdoor air dampers, check controls, measurements of carbon dioxide, temperature and relative humidity, sources near outdoor air intake, measure return and supply air volume, cleanliness of coils, liner and condensate pan)
  • inspection of exterior
  • inspection below drop ceiling (housekeeping, sink and floor drain traps, signs of past and present moisture concern via visual and/or moisture meter, mold growth, ensure connection of current and capping of abandoned sanitary vents, odorizers, excessive plants and fabric items, identify potential pathways, and measure volatile organic compounds, carbon monoxide, and lighting)
Findings

Date of Assessment: August 4, 2026

The Office of the Environment observed elevated relative humidity (>70%) within the areas serviced by Air Handling Units (AHUs) 3 and 4 during a summer walkthrough and informed Building Maintenance in order for them to investigate.

The Office of the Environment observed visible mold growth in the custodial office (Room 111).

No mold growth was observed in the other rooms serviced by AHUs 3 and 4.

The source of the mold growth is elevated relative humidity within the space due to the Heating Ventilation and Air Conditioning (HVAC) system being tripped while ongoing renovation activities occur. 

Corrective Actions
August 5th, 2026

Chiller was reset and observed to operating normally. 

August 7th, 2026

A board approved restoration contractor cleaned and disinfected mold impacted items and materials within Room 111. 

Closed
No
Tracking Number
CXXAES20260003CC