Concern: Long Reach High School: May 8th, 2019 (CXLRHS20190000D0)

Location
224
Date of IEQ Report Form
Date of Report
Concern
Room has a musty smell to it when first entering and just feel stagnate in the room. Has been like this for the past week.
IEQ Investigation Process

Identify deficiencies that may impact IEQ and/or sources of odor concerns. Typically includes the following depending on the nature of concern, but not limited to:

  • interview/questionnaire of concern individual(s)
  • inspection above drop ceiling (condition of roof deck, pipe insulation, return air plenum)
  • inspection of ventilation system (operation of variable air volume box and outdoor air dampers, check controls, measurements of carbon dioxide, temperature and relative humidity, sources near outdoor air intake, measure return and supply air volume, cleanliness of coils, liner and condensate pan)
  • inspection of exterior
  • inspection below drop ceiling (housekeeping, sink and floor drain traps, signs of past and present moisture concern via visual and/or moisture meter, mold growth, ensure connection of current and capping of abandoned sanitary vents, odorizers, excessive plants and fabric items, identify potential pathways, and measure volatile organic compounds, carbon monoxide, and lighting)
Findings

Date(s) of Assessment: May 23, 2019

No odors were present within the room during the assessment.

No odors were emanating from the rooms ceiling mounted Unit Ventilator.

No mold growth was identified. 

The condition above the drop-ceiling was assessed and was acceptable. 

No thermal anomalies indicative of moisture intrusion were noted.

The odor is likely associated with building materials and room supplies which are influenced by expected fluctuations of indoor and outdoor air temperatures and humidity levels. The unit ventilators fan operates continuously during scheduled hours of operation. The ventilation unit will not be cooling or heating if the room’s thermostat is satisfied. As a result, if the room's temperature set point is satisfied and weather outdoors is damp/humid, the ventilation will introduce unconditioned air into the space. "Musty/mold" odors are often reported under these circumstances.

Corrective Actions
June 6th, 2019

Building Services (HVAC) will visit the site to check the operation of the room's unit ventilator.

Closed
No
Tracking Number
CXLRHS20190000D0