Identify deficiencies that may impact IEQ and/or sources of odor concerns. Typically includes the following depending on the nature of concern, but not limited to:
- interview/questionnaire of concern individual(s)
- inspection above drop ceiling (condition of roof deck, pipe insulation, return air plenum)
- inspection of ventilation system (operation of variable air volume box and outdoor air dampers, check controls, measurements of carbon dioxide, temperature and relative humidity, sources near outdoor air intake, measure return and supply air volume, cleanliness of coils, liner and condensate pan)
- inspection of exterior
- inspection below drop ceiling (housekeeping, sink and floor drain traps, signs of past and present moisture concern via visual and/or moisture meter, mold growth, ensure connection of current and capping of abandoned sanitary vents, odorizers, excessive plants and fabric items, identify potential pathways, and measure volatile organic compounds, carbon monoxide, and lighting)
Date of Assessment: August 7, 2026
Visible mold growth was observed on concrete masonry unit (CMU) walls within the health suite bathrooms.
Condensation was observed on the exhaust fan.
The exhaust fan was found to be inoperable at the time of the assessment.
The observed mold growth is believed to be associated with elevated humidity levels resulting from the inoperable exhaust fans, which may have allowed moisture to accumulate within the space over an extended period of time.
The Office of the Environment cleaned impacted surfaces with a disinfectant.
Building Maintenance (HVAC) identified that the wire was not connected to the status relay preventing the exhaust fans from operating. Wire was reconnected and fans were verified to be operational.