| Check | OK | Comments |
|---|---|---|
| Tag Number | ||
Displayed
|
No
|
No tag numbers were observed on the exhaust fans.
|
| Status | ||
Running
|
No
|
AHU-5 - Not operational. The HVAC Department was contacted after this was observed.
|
| Check | OK | Comments |
|---|---|---|
| Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
| Louvers and Access Doors | ||
Operating properly
|
Yes
|
|
| Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
| Dampers | ||
Outside air damper: no obstructions
|
Yes
|
|
Return air damper: no obstructions
|
Yes
|
|
Assessor
Christopher Madden
Date
| Check | OK | Comments |
|---|---|---|
| Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
| Insulation | ||
Secure and Clean
|
Yes
|
|
| P-Trap (if present) | ||
Charged with liquid
|
Yes
|
|
Outdoor Temperature
78°F
| Check | OK | Comments |
|---|---|---|
| Filters | ||
Free of any bypassing
|
No
|
AHU-3 - Difficult to tell if bypass is occurring when doors are closed. Two pieces of wood were used as a spacer instead of one. There appears to be gaps when the door is opened.
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes
|
|
| Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
| Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
| Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes
|
|
Relative Humidity
45%
| Check | OK | Comments |
|---|---|---|
| Condition | ||
Operational
|
No
|
Various exhaust fans were not operational to include two out of the three fans on the high room (left side of school), several EFs on the backside of the school, and one of the two gymnasium fans.
|
No unusual odors, noise, or vibration
|
No
|
Exhaust fan (back of building) - Excessive Rattle.
|
Outdoor Dew Point
55°F
| Check | OK | Comments |
|---|---|---|
| Chilled Water Central Plant | ||
Chiller operational
|
Yes
|
|
| Heating Central Plant | ||
Boiler operational
|
Yes
|
|
Misc. Comments
Work Order #193571.
Work Order Number(s)
193571
Issues found durring this assessment have been assigned to the above
work order(s).