Identify deficiencies that may impact IEQ and/or sources of odor concerns. Typically includes the following depending on the nature of concern, but not limited to:
- interview/questionnaire of concern individual(s)
- inspection above drop ceiling (condition of roof deck, pipe insulation, return air plenum)
- inspection of ventilation system (operation of variable air volume box and outdoor air dampers, check controls, measurements of carbon dioxide, temperature and relative humidity, sources near outdoor air intake, measure return and supply air volume, cleanliness of coils, liner and condensate pan)
- inspection of exterior
- inspection below drop ceiling (housekeeping, sink and floor drain traps, signs of past and present moisture concern via visual and/or moisture meter, mold growth, ensure connection of current and capping of abandoned sanitary vents, odorizers, excessive plants and fabric items, identify potential pathways, and measure volatile organic compounds, carbon monoxide, and lighting)
Date of Assessment: October 6, 2026
General Information
The room is serviced by a unit ventilator (UV), which was observed leaking and subsequently reported to Building Services. On October 1, 2026, Building Services (HVAC) inspected the area and determined that a clogged drain line within the UV was causing condensate to enter the classroom. The drain line was cleared. The UV filter was visibly dirty but remained within its acceptable replacement interval. Relative humidity was measured at 70% at the time of the assessment which is above the acceptable upper range of 60%.
On October 2, 2026, the UV was found to be operating outside its scheduled hours as programmed in the building automation system (BAS). A faulty network card was identified as preventing communication between the UV and the BAS. The UV coils were cleaned, and the filter was replaced. The unit was also found to be overcooling the space, with a temperature setpoint of 66°F. The setpoint was adjusted to 71°F.
Custodial Services reportedly cleaned and extracted the carpet affected by the UV leak after the drain line was cleared on October 1, 2026.
Assessment Information (October 6, 2026)
The room contained a combination of vinyl floor tile and carpet flooring, concrete masonry unit (CMU) walls, and a suspended ceiling with drop-in ceiling tiles.
Temperature, relative humidity, and carbon dioxide (CO₂) measurements were collected within the space. All measurements were within acceptable ranges at the time of the assessment.
The carpet was evaluated for elevated moisture using a moisture meter. No elevated moisture was detected at the time of the assessment.
No unusual odors were observed during the assessment.
No obvious indications of moisture intrusion were identified within the room, except for a stained ceiling tile along the exterior wall. Water staining was also observed on the CMU wall above the ceiling tile grid near the stained ceiling tile.
Building Services reported that the staining was associated with a known building envelope issue. Repairs are planned as part of a future capital project.
The UV was operational at the time of the assessment. The filter was within the acceptable replacement interval, the coils and filter appeared generally clean, and no standing water was observed in the drain pan.
No visible mold growth was observed on the surfaces inspected above or below the ceiling tile grid.
No visible gnats were observed at the time of the assessment.
Visible dust deposits were observed on the ceiling grid near the supply diffusers.
Conclusion
Based on the above the following items may be contributing factors to the reported symptoms experienced:
- Visible dust deposits were observed within the space and may contribute to allergies
- Staff member reported presence of gnats earlier in the year (no evidence identified during October 6th assessment),
- Periods of elevated relative humidity, potentially caused by reported building envelope issues or the faulty network card on the UV, may have caused conditions conducive to dust mite proliferation.
The below corrective actions were performed to address health concern.
As a precautionary measure, the carpet was cleaned and extracted on October 16, 2026.
Visible dust deposits on ceiling grid were removed using a vacuum with soft brush attachment.
An assessment is to be scheduled to investigate reports of gnats and identify and address potential points of entry.
A contractor is to be scheduled to replace the faulty network card in the UV to restore communication with the BAS.