| Check | OK | Comments |
|---|---|---|
| Tag Number | ||
Displayed
|
Yes
|
|
| Status | ||
Running
|
Yes
|
|
| Check | OK | Comments |
|---|---|---|
| Outdoor Pollution | ||
Free from pollution sources w/i 25 ft. (e.g. dumpster, chimney, etc.)
|
Yes
|
|
| Louvers and Access Doors | ||
Operating properly
|
Yes Work Order Closed by Building Maintenance
|
Air Handling Unit (AHU-1) - Access door latch severely bent, unable to open the door.
|
| Deflectors & Screens | ||
Present
|
Yes
|
|
No debris
|
Yes
|
|
| Dampers | ||
Outside air damper: no obstructions
|
Yes Work Order Closed by Building Maintenance
|
Inconsistency on the position of the outside air dampers (OADs) from one unit to the other when comparing similar types of units. On some units, the OADs appear to be 100% open, while on others they are partially open. For example:
• AHU-4, AHU-6, AHU-7, and Kindergarten – The OADs are 100% open. At the time of walkthrough the outside air
temperature was approximately 46 deg. The OADs should not be 100% open at that temperature, it is too cold.
• AHU-8 – The OADs are less open by comparison.
The OADs were observed to be 100% closed on the following units:
• AHU-3 and AHU-5
|
Return air damper: no obstructions
|
Yes
|
|
Assessor
Hummy Khan
Date
| Check | OK | Comments |
|---|---|---|
| Clean | ||
No excess dirt, not used for storage
|
Yes
|
|
| Insulation | ||
Secure and Clean
|
Yes
|
|
| P-Trap (if present) | ||
Charged with liquid
|
Yes
|
|
Outdoor Temperature
46°F
| Check | OK | Comments |
|---|---|---|
| Filters | ||
Free of any bypassing
|
Yes
|
|
Correct size
|
Yes
|
|
Free from excessive loading, dampness or odor
|
Yes
|
|
Not collapsed/not fallen off
|
Yes
|
|
Present (not missing)
|
Yes
|
|
Date and initials written
|
Yes
|
|
| Heating Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
| Cooling Coils | ||
Clean, no noticeable leaks, or obstructions
|
Yes
|
|
Access: Free of any obstructions in area that may affect access
|
Yes
|
|
Condensation: No excess condensation problems
|
Yes
|
|
Blowoff: Free of water from coil blowoff
|
Yes
|
|
| Condensate Pan and Drain Line | ||
No visible bacterial or fungal growth
|
Yes
|
|
Clean, no residue, no standing water
|
Yes
|
|
No Overflow, leakage, blockage, or damage
|
Yes
|
|
Proper slope, drain line ok, drainage acceptable, discharge okay
|
Yes Work Order Closed by Building Maintenance
|
AHU-3 and AHU-7- Condensate drain improperly terminated.
|
Relative Humidity
38%
| Check | OK | Comments |
|---|---|---|
| Condition | ||
Operational
|
Yes
|
|
No unusual odors, noise, or vibration
|
Yes
|
|
Outdoor Dew Point
23°F
| Check | OK | Comments |
|---|---|---|
| Heating Central Plant | ||
Boiler operational
|
Yes
|
|
| Check | OK | Comments |
|---|---|---|
| Thermostat | ||
Thermostat setting acceptable
|
Yes
|
|
Thermostat cover
|
Yes
|
|
Fan Mode Correct
|
Yes
|
|
Space Temperature Acceptable
|
Yes
|
|
Work Order Number(s)
16001
Issues found durring this assessment have been assigned to the above
work order(s).