Concern: Long Reach High School: September 26th, 2018 (CXLRHS2018000055)

Location
Room 304
Date of IEQ Report Form
Date of Report
Concern
A "mold" odor was sensed when entering the room. A general health symptom was reported.
IEQ Investigation Process

Identify deficiencies that may impact IEQ and/or sources of odor concerns. Typically includes the following depending on the nature of concern, but not limited to:

  • interview/questionnaire of concern individual(s)
  • inspection above drop ceiling (condition of roof deck, pipe insulation, return air plenum)
  • inspection of ventilation system (operation of variable air volume box and outdoor air dampers, check controls, measurements of carbon dioxide, temperature and relative humidity, sources near outdoor air intake, measure return and supply air volume, cleanliness of coils, liner and condensate pan)
  • inspection of exterior
  • inspection below drop ceiling (housekeeping, sink and floor drain traps, signs of past and present moisture concern via visual and/or moisture meter, mold growth, ensure connection of current and capping of abandoned sanitary vents, odorizers, excessive plants and fabric items, identify potential pathways, and measure volatile organic compounds, carbon monoxide, and lighting)
Findings

The room is serviced by a unit ventilator.

No mold or mold odors were observed at the time of the assessment.

A "carpet" odor was observed when entering the room.

No elevated moisture was detected in the carpet.

No thermal anomalies indicative of moisture intrusion were observed.

The odor may have been associated with building materials and room supplies which are influenced by expected fluctuations of indoor and outdoor air temperatures and humidity levels. The unit ventilators fan operates continuously during scheduled hours of operation. The ventilation unit will not be cooling or heating if the rooms thermostat is satisfied. As a result, if the room's temperature set point is satisfied and weather outdoors is damp/humid, the ventilation will introduce unconditioned air into the space. "Musty/mold" odors are often reported under these circumstances.

Closed
Yes
Date Closed
Tracking Number
CXLRHS2018000055